Domestic Hot Water Ez Setup - Exalt Combi Units; Altitude Setup - IDEAL EXALT Solo 110 Installation & Maintenance Manual

Hide thumbs Also See for EXALT Solo 110:
Table of Contents

Advertisement

CHAPTER 9 - CTRLMAX OPERATION
9.9.
Domestic Hot Water EZ Setup
Domestic Hot Water EZ Setup allows the installer to quickly customize the Domestic Hot Water settings for the application
EZ Setup
DHW EZ Setup
DHW Setpoint
140°F
68°F
Warmstart Temperature
86°F
O

9.10. Altitude Setup

Combi
88°F
ENTER ACCESS CODE
84°F
Target = - -
CH & DHW Settings
0 5 [4]
Standby
CH Settings
- EXALT Combi Units
168°F
DHW
125°F
140°F
DHW
Warmstart Hysteresis
30°F
9
36°F
EZ Setup Complete
DHW EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
Boiler Settings
Boiler Settings
Model
Combi
Lockout Temp.
210ºF [99ºC]
Boiler Settings
Modbus Address
1
Pump Settings
Pump Settings
Ignition level
300rpm
Mix zone high limit
Ignition level
114ºF
3000 rpm
Altitude
Mix zone high limit
114ºF
WP diff trigger
0cpsi
Appliance setting
Altitude
0ft
4920ft
0ft
19680ft
DHW EZ Setup prompts the installer to select the DHW setpoint.
DHW Setpoint prompts to enter the fixed setpoint temperature
during a domestic hot water call.
Touch the
or
soft keys to adjust the temperature setpoint
to store the setting. The DHW Warmstart Tempera-
then touch
ture screen then appears .
Default: 140°F
[60°C].
DHW Warmstart Temperature prompts to enter the DHW tem-
perature in case you want to speed up the delivery of DHW in sum-
mer conditions.
Touch the
or
soft keys to adjust the temperature then touch
to store the setting. At the minimum temperature (86°F), this
function is OFF. The DHW Warmstart Hysteresis screen then ap-
pears .
Default: 125°F
[52°C].
DHW Warmstart Hysteresis prompts to enter the DHW hysteresis
value, comprised between 9°F (5K) and 36°F (20K).
Touch the
or
soft keys to adjust the hysteresis value, then
touch
to store the setting.
Default: 30°F
(17k).
Altitude must be correctly set to allow reliable operation of the
boiler.
From the home screen touch the
seconds and "Enter Access Code" screen will be shown.
Touch the
or
soft keys to set the access code to 054. Touch
and the CH & DHW Settings creen will be shown.
Touch
and the CH Setting screen will be shown. Touch the
soft key and the "Boiler Settings" (list) screen will be shown.
Touch the
soft key until the "Altitude" option is highlighted.
Touch
and the Altitude screen will be shown.
Touch the
soft key until the correct altitude is shown, then touch
the
soft key to highlight the home icon. Touch
Note. The altitude moves in steps of 984 ft (300m).
or
soft keys simultaneously for 5
to confirm.
59

Advertisement

Table of Contents
loading