Hole Type
Endcap Hole (optional) The distance between an endcap hole and the next hole is
Sampling Holes
28
Table 9-4: Sampling Hole Positioning
Notes
less than or equal to 10 meters.
Refer to the holes labelled A in Figure 9-1.
The distance between sampling holes is less than or equal to
10 meters.
Refer to the holes labelled B-F in Figure 9-1.
Figure 9-1: Predesigned Pipe Network Example