IAS-2 Product Guide
4.3.1
Configuration with two Addressable Detectors
The following schematic shows detectors wired directly to the loop with the FAULT 2 relay connected to loop
via addressable module.
Figure 4-1: Wiring diagram for an IAS-2 system with two addressable detectors
4.3.2
Configuration with Conventional Detectors
The terminating resistor is wired across both fault relays so a flow fault in either channel will produce a zone
fault.
Figure 4-2: Wiring diagram for an IAS-2 system with two conventional detectors
4.3.3
Configuration with Units Connected in Series
The schematic shows the first and last units in a chain of IAS-2 units. Zone circuit wiring is returned from last
unit to first via fault relay contacts in each unit and a terminating resistor fitted to first unit as shown. A flow
fault condition in any unit will break the connection to the terminating resistor and indicate a zone fault without
affecting the operation of the detectors themselves.
10
ICAM by Xtralis