24D-2 REFRIGERATOR
system is to measure the number of amps
drawn by the compressor when connected to a
120-volt source.
This is done by removing one of the com-
pressor
leads and connecting
a 0-5 A .C.
ammeter in series with the compressor (figure
2). A reading of 2 amps should be read for the
six cubic foot model and approximately 2 .6
NORCOLD
REFRIGERATOR SPECIF
amps for the seven and one-half cubic foot
model .
If the amperage reading is high, this is an
indication the system is undercharged.
If a
low
reading
is
obtained
the
system
is
overcharged
If it is determined that the
system is under or overcharged, the entire
cooling system must be replaced.
CATIONS
Model
6 Cubic Foot
7 .5 Cubic Foot
Compressor Power
40 Watts
60 Watts
Compressor Amps Required
2 Amps
2 .6 Amps
Compressor Volts Required
19 to 21
22 to 24
(A .C . Operation)
Volts A .C .
Volts A .C .
Compressor Volts Required
27 .2 to 29 .2
31 .5 to 33 .5
(D.C . Operation)
Volts A .C .
Volts A .C .
Compressor Motor Resistance
2 to 3 Ohms
2 to 3 Ohms
Compressor Motor Speed
60 Strokes/Sec.
60 Strokes/Sec .
Inverter Output
11 Volts A .C .
11 Volts A .C.
Transformer Output
20 Volts A .C .
23 Volts A .C .
Input Voltage
12 Volts A .C .
12 Volts D .C.
or 120 Volts A .C .
or 120 Volts A .C .
Refrige ra nt
R 12
R 12
Refrigerant Charge
2.56 Ounces
17 Ounces