Benchmark Platinum-Edge [ii]: Installation Manual
SECTION 2 – INSTALLATION
Connector Strip J6 Terminals
Pin # Name
1
Remote Interlock Out
2
Remote Interlock Return
3
Delayed Interlock 1 Out
4
Delayed Interlock 1 Return
5
Delayed Interlock 2 Out
6
Delayed Interlock 2 Return
Connector Strip J7 Terminals
Pin # Name
1
Spare 2 Relay N.O.
2
Spare 2 Relay Com
3
DHW Pump Relay N.O.
4
DHW Pump Relay Com
5
V2/Spare 1 Relay N.O.
6
V2/Spare 1 Relay Com
7
Backup Relay N.O.
8
Backup Relay Com
9
Swing Valve 1 Relay N.O.
10
Swing Valve Relay Com
11
Fault Relay N.O.
12
Fault Relay Com
13
Aux Relay N.O.
14
Aux Relay Com
Connector Strip J14 Terminals
Pin # Name
BAS RS485 +
1
OMM-136_E • GF-210 •
Description
Connection to an auxiliary device interlock, such as louver open
feedback or flow sensor.
Connection to an auxiliary device interlock that requires a delay before
the plant starts firing.
Connection to an auxiliary device interlock that requires a delay before
the plant starts firing.
Description
Connection to an auxiliary device enable/disable signal, such as:
System Pump
Summer Pump
Pump 2
Louver
Louver 2
Damper
Other
To assign/program its function, go to the Controller's
Advanced Setup → Ancillary Devices →
Relay to Spare 2 Relay and the Name to one of the above devices.
Connection to a DHW Pump enable/disable signal.
Connection to an auxiliary device enable/disable signal, such as:
Swing Valve 2
System Pump
Summer Pump
Pump 2
To assign/program its function, go to the Controller's
Advanced Setup → Ancillary Devices →
Relay to V2/Spare 1 Relay and the Name to one of the above
devices.
Connection to a reserve/backup boiler enable/disable signal.
Connection to a Swing Valve 1 enable/disable signal.
Connection to a Fault/Remote Alarm enable/disable signal.
Connection to an auxiliary device enable/disable signal.
Description
Connection to the building automation system (BAS) network (Modbus RTU,
12/13/2019
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Main Menu →
Relays, then set the
Louver
Louver 2
Damper
Other
Main Menu →
Relays, then set the
Page 39 of 57