14 Option description
STO function activation and indication response times
Module response times only
STO activation and indication response times
STO activation response time
STO indication response time
1)
STO activation response time = delay between de-energizing the STO input and switching off the drive/
inverter output bridge
2)
STO indication response time = delay between de-energizing the STO input and indication of STO input de-
energization
Response times with typical safety relay
STO activation and indication response times
STO activation response time
STO indication response time
3)
STO activation response time = delay between de-energizing the STO relay and switching off the drive/
inverter output bridge
4)
STO indication response time = delay between de-energizing the STO relay and indication of STO input de-
energization
Typical response time
1)
2 ms
2)
1.5 ms
Typical response time
3)
52 ms
4)
51.5 ms
Maximum response time
20 ms
-
Maximum response time
70 ms
-