Sto Status Indications - ABB ACS800 Series Application Manual

Industrial drives, safe torque off function (+q967)
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

The table below describes the operation of the STO function in detail depending on:
status of the STO inputs
the fault or warning START INHIBI (see chapter
Status of STO inputs
De-energized
One energized, other
de-energized
Energized

STO status indications

Note: The indications are not safety classified information.
Control program
System Control Program
Standard Control Program
Control program
System Control Program
Standard Control Program
Control program
System Control Program
Standard Control Program
See also chapter
Maintenance and fault
When drive is
How the STO function operates
running
Awakes and trips the drive.
stopped
Awakes and disables start.
running
Awakes and trips the drive.
stopped
Awakes and disables start.
STO is on standby. Drive operates
running or stopped
normally.
Alarm and status bits / words
08.02 AUX STATUS WORD bit 8
08.21 START INHIBI WORD
03.03 AUX STATUS WORD bit 8
Alarms and faults
09.04 ALARM WORD 1 bit 0
09.06 FAULT WORD 3 bit 5
31.02 START INHIBIT ALM
03.08 ALARM WORD 1 bit 0
Digital / relay outputs
14 DIGITAL OUTPUTS
Note: To be programmed by the user. For information on
programming the digital outputs, see ACS800 system control program
firmware manual (3AFE64670646 [English]).
14 RELAY OUTPUTS
Note: To be programmed by the user. For information on
programming the relay outputs, see ACS800 standard control
program firmware manual (3AFE64527592 [English]).
tracing.
Option description 13
Maintenance and fault
tracing).
START INHIBI
indication
Fault
Warning
Fault
Warning
-

Advertisement

Table of Contents
loading

Table of Contents