5.2.1 Wiring Requirements ............................... 12 5.2.2 Adding the DTS 310 to an existing LonWorks Network via Service Pin..............12 5.2.3 Adding the DTS 310 to an existing LonWorks Network via Neuron ID ..............12 ..............................13 THERNET OMMUNICATIONS )..........................13...
The one revenue grade meter for all applications. Your DTS 310 energy sub-meter is one of the most versatile meters available on the market. The DTS 310 can operate in any environment, requires no external power source to operate, and works with all UL or ETL listed 333mV current transformers.
The DTS 310 is intended for 480V L-L Measurement Category III use. Do NOT exceed this usage. Use the model number of the DTS 310 to verify that it is suitable for the voltage, type and category of the installation.
DC Auxiliary Power Section 3.1 pg 8 Voltage Connections Current Connections Section 3.1 pg 8 Section 3.1 pg 8 DTS 310 Meter Model Number ETL Mark Digital I/O Remote Communications Section 5.4 pg 13 Section 5 pg 11 Serial Communications Ethernet Communications Section 5.1 pg 11...
Before handling the DTS 310 ensure that all power running to the DTS 310 is removed. The DTS 310 is for indoor use only, and MUST be mounted in a NEC compliant enclosure suitable for the environmental conditions and locked with a user supplied lock.
Mount the DTS 310 as close as possible to the electrical panel being monitored. Make sure that there is at least 4” of clearance above and below the DTS 310 for wiring and connector clearance and ¼” of clearance on both sides for cooling.
CONNECTING TO THE DTS 310 Wiring Voltage and Current Inputs ATTENTION Make sure that your model of DTS 310 is approved for the following wiring guidelines. Note: CTs should be connected to the same panel as the voltage connections. 3.1.1 Wiring Examples Load...
The measured phase current will be the total current across all the loads on that phase. The CT primary rating for the DTS 310 must be set to the CT rating * Number of CT sets. The example below shows how to calculate the service current for figure 3.2.1.
DC Auxiliary Power The most common way to power the DTS 310 meter is through the voltage connections. If this situation is not ideal the DTS 310 meter can be powered through a user supplied DC source. ATTENTION Check the DTS 310 model number for the correct DC voltage to power the DTS 310 through the auxiliary.
If additional maintenance is needed, please contact Measurlogic Inc. DTS 310 COMMUNICATIONS INTERFACE The DTS 310 has 4 options for outputting data as well as the several communication protocols depending on the model ordered: 2-Wire RS-485 bus ...
Use 18-22 AWG; 2 core; twisted pair cable. LonWorks TP/FT – 10 ports are non-polarity sensitive. DTS 310 meters fitted with LonWorks TP/FT – 10 communications can be wired in bus, star, or ring topologies. 5.2.2 Adding the DTS 310 to an existing LonWorks Network via Service Pin ...
The DTS 310 comes with a Digital I/O port that can be configured for pulse outputs. The DTS 310 will pulse at 1kWh by default but can be changed using DTS Config or by setting the DIP switches found on the side of the meter.
5.5.1 Configuring DIP Switches – Modbus RTU The following table shows how to use the DIP Switches to manually configure a DTS 310 for a Modbus RTU network. The Modbus Address is set by flipping the switches 2-8 ON (▼) that add up to the desired address.
LED Definitions The DTS 310 is equipped with 3 LEDs useful for diagnostics and troubleshooting – STATUS, REMOTE, and PULSE. Status LED The STATUS LED consists of a repetition of two flashes and shows whether the measured power is being ...
Regular cleaning of the DTS 310 is NOT required, but if you do wish to clean the DTS 310, please note the following: Before attempting to clean the DTS 310 ensure that all power running to the DTS 310 is removed. ...