Delta AlertMaxx Installation & Operating Instructions Manual

Pump station high level alarm

Advertisement

Quick Links

Pump Station High Level Alarm
AlertMaxx™
Installation & Operating Instructions
For Ground Water (DMS-270) & Foul Water (DMS-269)
T.
01992 523523
E.
info@deltamembranes.com
W.
www.deltamembranes.com
Rev 4

Advertisement

Table of Contents
loading

Summary of Contents for Delta AlertMaxx

  • Page 1 Pump Station High Level Alarm AlertMaxx™ Installation & Operating Instructions Rev 4 For Ground Water (DMS-270) & Foul Water (DMS-269) 01992 523523 info@deltamembranes.com www.deltamembranes.com...
  • Page 2 All rights reserved. Contents provided herein must neither be distributed, copied, reproduced, edited or processed for any other purpose, nor otherwise transmitted, published or made available to a third party without express written consent from Delta Membranes. Subject to technical modification without prior notice.
  • Page 3: Table Of Contents

    Installing a pendant float into a foul water chamber 10.0 Connecting a pendant float to the AlertMaxx unit 11.0 Activating & testing the AlertMaxx unit 11.1 Turning on the AlertMaxx unit for the first time 11.2 Testing the AlertMaxx unit 12.0 Connecting external devices 13.0 Servicing...
  • Page 4: Alertmaxx Overview

    This high level alarm is designed to alert home owners when the water level in their pump chamber becomes too high. The unit will also inform home owners when a service is due on their pump station. CAUTION! The AlertMaxx should be installed by a qualified tradesperson. Box contents Cardboard box contents •...
  • Page 5: Technical Information

    Approximate Installation time 30 minutes Unit location The AlertMaxx must be positioned in an area where the alarm can be clearly heard and is permanently accessible. CAUTION! The AlertMaxx unit is not waterproof and must be installed indoors or inside a kiosk.
  • Page 6: Connecting Mains Power To The Alertmaxx Unit

    BLUE Connecting mains power to the AlertMaxx unit Insert a large cable gland into the far right hole of the AlertMaxx unit. Feed the mains power cable through the right hand cable gland (large) and connect the power cable to the terminal strip (see figure 2).
  • Page 7: Installing A Finger Float Into A Ground Or Surface Water Chamber

    Installing a finger float into a ground or surface water chamber Care must be taken to ensure the correct type of float switch is installed into the chamber. The AlertMaxx is sold either with a finger float or pendant float. The finger float must only be used for ground water applications and the pendant float must only be used for foul water applications.
  • Page 8: Connecting A Finger Float To The Alertmaxx Unit

    Using a draw cord, pull the float cable through the cable duct on the chamber. Insert a large cable gland into the second from right hole of the AlertMaxx unit. Pull the float cable through the small cable gland on the AlertMaxx unit.
  • Page 9: Installing A Pendant Float Into A Foul Water Chamber

    AlertMaxx Installing a pendant float into a foul water chamber Option 1 - Free standing foul pump Using the cable tie provided, attach the float cable to the discharge arm allowing the bottom of the float switch to hang approximately 200mm above the base of the chamber (see figure 6).
  • Page 10: Connecting A Pendant Float To The Alertmaxx Unit

    Using a draw cord, pull the float cable through the cable duct on the chamber. Insert a large cable gland into the second from right hole of the AlertMaxx unit. Pull the float cable through the large cable gland on the AlertMaxx unit.
  • Page 11: Activating & Testing The Alertmaxx Unit

    LED every 5 seconds. Refit the front fascia. Turn on the mains power supply to the AlertMaxx unit. The beep and red flash from step 4 will stop after approximately 30-60 seconds. CAUTION! If the battery is misconnected to the AlertMaxx (i.e.
  • Page 12: Connecting External Devices

    AlertMaxx 12.0 Connecting external devices The AlertMaxx unit has volt free contacts to connect external devices such as an alarm or beacon. When the alarm is activated the relay sends a signal once every second. The volt free relay is designed to accept devices with a maximum load of 0.5A and voltage up to 30V.
  • Page 13: Servicing

    AlertMaxx 13.0 Servicing The AlertMaxx unit will alert home owners when their pump station requires servicing. This is indicated by the blue LED flashing every second followed by one beep every minute. The beep can be muted by pressing the ‘RESET’ button. The beep will return 7 days from pressing the ‘RESET’ button until a service technician resets the alarm unit.
  • Page 14: Led Codes

    AlertMaxx 15.0 LED codes Beep Red LED Blue LED Green LED Fault 1/sec 3/sec High water alarm 1/min 1/5sec 1/sec Mains failure Solid Error - Call support 1/min 1/sec Service required 2/sec High water has occurred 1/sec All OK All flash in sequence...
  • Page 15 AlertMaxx Figure 1. (Scale 1:1) Mounting hole positions For technical support, please call 01279 757400...
  • Page 16 After Sales Service All Delta Membrane pump systems are fitted & can be maintained by our partners, Packaged Pump Systems. With our long-term relationship we ensure that the system selected is fit for your requirements, is delivered on time, professionally installed & offers hassle free on-going operation & maintenance.