5. Maintenance and Troubleshooting

5.1 Overview

This chapter contains operational test procedures, troubleshooting, cleaning, and maintenance, instructions.
IMPROPER MAINTENANCE
Strictly adhere to all maintenance and troubleshooting instructions.
Failure to comply with these instructions could result in death or serious injury.

5.2 Operational Test

To ensure operational readiness, perform the operational test at least once a day and every time the light curtain is
repaired or the installation is changed. The operational test consists of passing a test rod (included with the FF-SYA14
or FF-SYA30 units) or the hand (for the FF-SYA60 units or the FF-SYA234 multibeam systems) through the sensing
field to ensure the light curtain will detect it (see Figure 5-1). The sensing function of the light curtain shall be actuated
by moving the relevant test rod at a maximum speed of 2,5 m/s for the FF-SYA14 and the FF-SYA30 (or by moving the
hand at a maximum speed of 1,6 m/s for the FF-SYA60 and the FF-SYA234). The included test rod will have a
diameter equal to the resolution of the light curtain.
Light Curtain
FF-SYA14
FF-SYA30
FF-SYA60
FF-SYA234 Multibeam System
FF-SYA02500
FF-SYA03400
FF-SYA04300
Figure 5-1 Operational Test with the Test Rod
107031-33-EN FR26 GLO 1101 Printed in France
Sensing range
Test Rod
Emitter
Resolution
14 mm / 0.6 in
30 mm / 1.2 in
60 mm / 2.4 in
Beam Spacing
500 mm / 19,7 in
400 mm / 15,76 in
300 mm / 11,82 in
Receiver
55