Limitations - Siemens RVP201 Basic Documentation

Heating controllers
Table of Contents

Advertisement

Frost protection for the
boiler
Note
Maximum limitation of
flow temperature
Maximum limitation of
boiler temperature
Siemens
Building Technologies
This means that the minimum burner running time has priority. To be considered is the
boiler temperature's maximum limitation however, which always switches the burner off.)
T
K
Y
B
1
0
SD
Switching differential
t
Time
T
Boiler temperature
K
w
Boiler temperature setpoint
TK
x
Boiler temperature actual value
TK
Y
Burner control signal
B
Frost protection for the boiler uses fixed values:
Switch-on point: 5 °C boiler temperature (= minimum limit value)
Switch-off point: minimum limit value of boiler temperature + switching differential.
For the switching differential, the value set for control will be adopted
During quick setback or when there is no demand for heat, the boiler will be shut down,
that is, no defined minimum temperature will be maintained.
If, however, the boiler temperature falls below 5 °C, the burner will always be switched
on until the boiler temperature has exceeded the minimum limit value of the boiler tem-
perature by the amount of the switching differential. This always ensures a minimum
boiler temperature of 5 °C.
3.3.8

Limitations

The maximum limitations are no safety functions! For this purpose, devices such as
thermostats, limit thermostats, etc., are to be used.
Maximum limitation of the flow temperature can be set in the range 10...100 °C.
At the limit value, the heating curve runs horizontal. This means that the flow tempera-
ture setpoint cannot exceed the maximum value.
This function can be disabled.
Maximum limitation of the boiler temperature can be set in the range 10...100 °C.
The burner's switch-off point cannot be higher than the maximum limit value. In that
case, the switch-on point will be lower by the amount of the set switching differential.
This function can be disabled.
Heating controllers RVP201 and RVP211
3 Technical design
T
Kx
T
+ 0,5 × SD
Kw
T
Kw
T
- 0,5 × SD
Kw
t
21/46
CE1P2464en
2017-07-21