Register 40129: Diagnostics

Register Designation of the SIPROTEC objects
0
40129/2
Device OK
1
40129/2
Settings Calc.
2
40129/2
ProtActive
3
40129/2
Error Sum Alarm
4
40129/2
Alarm Sum Event
5
40129/2
Relay PICKUP
6
40129/2
Relay TRIP
7
40129/2
<user-defined>
8
40129/2
Test mode
9
40129/2
<user-defined>
10
40129/2
<user-defined>
11
40129/2
<user-defined>
12
40129/2
<user-defined>
13
40129/2
<user-defined>
14
40129/2
<user-defined>
15
40129/2
Data invalid
SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2240-A320-3
• Registers are write-protected.
• The contents of this register are also readable using function "Diagnostics" (function
code 8), subfunction "Return Diagnostic Register" (function code 2).
• Ref. to chap. "Bus-specific parameters" in the manual "SIPROTEC Communication
module, Modbus - Communication profile" (ref. to page 3) regarding signaling of
"Data invalid" (ref. to register 40129/2
1.
A write access is rejected with exception code 03 (ILLEGAL_DATA_VALUE).
1
15
).
Comment
1 = Update of the device replica in the SIPROTEC
device completed after initial start or restart
1 = Setting calculation is running
1 = At Least 1 Protection Funct. is Active
1 = Error with a summary alarm ON
1 = Alarm summary event ON
1 = Relay PICKUP (group signal)
1 = Relay GENERAL TRIP command
not pre-allocated
1 = Test mode is active
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
1 = Data in the Modbus message are invalid.
(This indication is created by the Modbus slave; not
available in DIGSI and not relocatable.)