7SR210 & 7SR220 Applications Guide
Directional overcurrent elements allow greater fault selectivity than non-directional elements for interconnected
systems where fault current can flow in both directions through the relaying point. Consider the network shown in
fig. 2.6-3.
The Circuit breakers at A, B, E and G have directional overcurrent relays fitted since fault current can flow in both
directions at these points. The forward direction is defined as being away from the busbar and against the
direction of normal load current flow. These forward looking IDMTL elements can have sensitive settings applied
i.e. low current and time multiplier settings. Note that 7SR22 relays may be programmed with forward, reverse
and non-directional elements simultaneously when required by the protection scheme.
A
B
C
D
E
G
Load

Figure 2.6-3 Application of Directional Overcurrent Protection

©2011 Siemens Protection Devices Limited