Error Diagnosis; Fault Identification At The Operation Unit Extinguishing B3Q440 - Siemens Cerberus CS1140 Commissioning Extinguishing

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

All 3 LEDs flashing = Operating unit ex-
tinguishing in mode 'Error diagnosis'
Line 'Sector valve'
Line 'Main valve'
Line 'Extinguishing horn'
Differentiation between open line/short circuit:
− slow flashing
= open line
− rapid flashing
= short circuit
Fire & Security Products
Siemens Building Technologies Group
8

Error diagnosis

All faults at the inputs/outputs of the E3G080 are individually displayed at the AlgoPilot. For
each of the 4 outputs an LED is provided on the E3G080 for error diagnosis (see chapter 4.2).
Separate LEDs are not provided for the inputs, but a special mode enables the identification of
each faulty or deactivated input and output.
8.1
Fault identification at the operation unit
extinguishing B3Q440
NOTE
Functions only when a fault is pending
Procedure:
1. If fault set switch 'S1' (E3G080) to 'ON'
2. Press 'S4' key (E3G080) once
3. LEDs 'Fire detector activated' / 'Evacuation' and 'Extinguishing released' flash simulta-
neously
4. Identify the input/output concerned according to the diagram below
Cerberus
Fire detector
activated
Evacuation
Extinguishing
released
Fault
System ON
5. Cancelling function: Set switch 'S1' to 'OFF'
B3Q440
Automatic
Line 'Illuminated warning panel'
release
blocked
Autom.+Man.
Line 'Manual activation'
release
blocked
Switch off
Line 'Stop-/blocking button'
sounder
Switch off
Line 'Extinguishing agent loss'
warning
panel
Line 'Extinguishing blocked'
Emergency
stop
Line 'Extinguishing released'
Loss of extinguishing
agent
17
005109_b_en−2