Carrier AQUASNAP 30RA B Series Manual page 12

Pro-dialog plus air-cooled liquid chillers with integrated hydronic module
Table of Contents

Advertisement

Compressor usage and electrical data
COMPRESSOR
Reference code
I Nom
I Max
DQ 12 CA 001EE
14.0
19.1
DQ 12 CA 002EE
16.2
22.1
DQ 12 CA 031EE
21.9
28.3
DQ 12 CA 036EE
24.5
32.8
Legend:
I Nom Nominal current draw at Eurovent conditions (see definition of conditions under nominal unit current draw), A
I Max Maximum operating current at 360 V, A
LRA
Locked rotor current, A
* With option 25 (electronic starter) the LRA value is reduced by 40%; the maximum start-up time per compresor is <0.8 seconds.
Short-circuit stability and protection
30RA
Short-term short-circuit stability (1s)
Without fuse
rms value/peak
kA*
040-080
5/7.5
090-160
8/15
200
8/15
240
8/15
*
This value corresponds to the switch/disconnect capacity, to the power distribution bus bar system capacity (if used) and to the protection circuit capacity in the standard
unit.
**
If the short-circuit current is higher, the unit can be protected by the fuse shown for the specific level.
The fuses (not supplied for Carrier units) are as recommended, to be installed upstream of the unit.
For unit sizes 040 to 160 a fused disconnect switch, equipped with fuses, can be installed in place of the standard unit switch. This should be done on site; please
contact the local service department or a qualified electrician. Alternatively please order the special version from the factory by contacting your local Carrier dealer.
For unit sizes 200 and 240 the installation requires drilling a hole into the control box, changing of the front door, and adapting the bus bar to be able to install the new
fused disconnect switch which is larger than the one used for the standard units.To order this special version from the factory, contact your local Carrier office.
List of recommended components with Siemens reference details:
30RA
Fused disconnect
040-080
80 A: 3KL7114-3AA00
090-160
160 A: 3KL7123-3DA00
200-240
200 A: 3KL7131-3AA00
224 A + 250 A: 3KL7132-3AA00
240
315 A: 3KL7141-3AA00
400 A: 3KL7142-3AA00
*** Shows the new protection values with higher-capacity fuses than those specified in the previous column. If such fuses are part of the electrical installation upstream of
the unit, this is sufficient as anti-short circuit protection to the specified level, without additional protection.
**** If a protection device, other than the recommended fuses above, is used for the installation to ensure that no additional protection is required, the protection device must
have the specified thermal limit (I
the specified protection fuses from the previous columns must be installed.
12
30RA
LRA*
Circuit
040
050
130
A
A1
B
130
A
A2
B
145
A
B
155
A
A1
B
With fuse
rms value
kA **
80A gL:50
160A gL:100
200A gL:100
250A gL:50
Contact protection
3KX71-32-1AA00
3KX71-32-2AA00
3KX71-32-3AA00 +
3KX71-31-3AA00 +
3KX71-31-3AB00
3KX71-32-4AA00 +
3KX71-31-4AA00 +
3KX71-31-4AB00
2
t) and limit effect characteristics for the short-circuit current. If the protection device does not have the specified characteristics, one of
060
070
080
090
B1
A1
B2
A2
A1+A2
A1+A2
A1
Other fuses
rms value
kA***
100A gL:30
125A gL:25
160A gL:6
200A gL:35
224A gL:40
250A gL:35
N/A
Control handle
NH Fuses
Use from disconnect switch
80 A 00gL: 3NA3 824 (3 off)
of the standard unit
160 A 00gL: 3NA3 836 (3 off) 50
3KX7112-4AA00
200 A 1gL: 3NA3 140 (3 off)
224 A 1gL: 3NA3 142 (3 off)
250 A 1gL: 3NA3 144 (3 off)
3KX7112-4AA00
315 A 2gL: 3NA3 252 (3 off)
400 A 2gL: 3NA3 260 (3 off)
100
120
140
160
A1
B1
B1
A2
A1+A2
B2
B2
B1+B2
A1
A1+A2
B1+B2
Other protection type
2
2
I
t (A
s)/peak limit
kA****
19200/12
155000/20
280000/20
550000/25
New protection level with fused
disconnect switch, rms value, kA**
100
200 A gL: 50
224 A gL: 50
250 A gL: 50
315 A gL: 40
400 A gL: 30
200
240
A1+A2
A1+A2+A3
B1+B2+B3 B1+B2+B3