9287500995 Rev B
47
meter value text box also displays it. Any value within the range can either be input to meter value text
box or selected by dragging the pointer in the meter using mouse. This value can then be sent to the unit
by pressing Send button.
The setpoint value currently set in the unit by any of the above methods is displayed in the current
setpoint textbox. To return to the nominal setting the button adjacent to PF Setpoint (Nominal) should be
pressed. If the PF Analysis screen is left without returning to nominal setpoint a message box is shown
(Figure 30) which allows the user to return to nominal setpoint by pressing YES or remain at the current
setpoint by pressing NO.
Figure 30. Message Box to Return to PF Nominal Setpoint
VAR Tab
Figure 31 illustrates the settings, sensing values, and alarm signal indicators of the VAR tab. Each setting
of the VAR tab is described in the following paragraphs.
VAR Step Response - VAR Setpoint (Nominal). This read-only field indicates the VAR setpoint. (The VAR
setpoint is set by using the Setpoint tab of the Setting Adjustments screen). The value displayed in the
VAR Setpoint field is selected by clicking the adjacent button. Clicking this button sends the VAR Setpoint
value to the BE2000E and changes the color of the button from gray to red.
VAR Step Response - Increment of VAR setpoint. This field indicates the increase that occurs to the VAR
setpoint when the corresponding increment button is clicked. Any setpoint value within the range and
higher than setpoint value can be input to this filed. The VAR setpoint changes to this value when the
adjacent button is clicked. When clicked, the Increment button changes from gray to red to indicate that
the VAR setpoint has increased to the value in the field.
VAR Step Response - Decrement of VAR setpoint. This field indicates the decrease that occurs to the
VAR setpoint when the corresponding decrement button is clicked. Any setpoint value within the range
and lower than the setpoint value can be input to this field. The VAR setpoint changes to this value when
the adjacent button is clicked. When clicked, the Increment button changes from gray to red to indicate
that the VAR setpoint has decreased to the value in the field.
VAR Step Response - Meter. The meter in the VAR tab shows the value selected. If an VAR setpoint
value is sent by increase, decrease or setpoint button the meter shows the corresponding value and
meter value text box also displays it. Any value within the range can either be input to meter value text
box or selected by dragging the pointer in the meter using mouse. This value can then be sent to the unit
by pressing Send button.
The setpoint value currently set in the unit by any of the above methods is displayed in the current
setpoint textbox. To return to the nominal setting the button adjacent to VAR Setpoint (Nominal) should
be pressed. If the VAR Analysis screen is left without returning to nominal setpoint a message box
(Figure 32) is shown which allows the user to return to nominal setpoint by pressing YES or remain at the
current setpoint by pressing NO.
BE2000E
BESTCOMS™ Software