9. Technical data

9.1 Minimum water flow requirements
for submersible pump motors
Casing or
Motor
sleeve I.D.
diameter
[inches]
4
5
4"
6
7
8
Notes:
A flow inducer or sleeve must be used if the
water enters the well above the motor or if
there is insufficient water flow past the motor.
The minimum recommended water velocity
over 4" motors is 0.25 feet (0.08 m) per
second.

9.3 Electrical data

4-inch, single phase, 2-wire motors (control box not required)
Volt
Hp
Ph
S.F.
[V]
0.5
1
230
1.60
0.75
1
230
1.50
1
1
230
1.40
1.5
1
230
1.30
Volt
Hp
Ph
S.F.
[V]
0.5
1
230
1.60
0.75
1
230
1.50
1
1
230
1.40
1.5
1
230
1.30
Min. flow past
the motor
[gpm]
1.2
7
13
21
30
Grundfos submersible pump motors - 60 Hz
Amperage
Full
Lock
S.F.
load
rotor
amps
4.5
34.5
6.0
6.9
40.5
8.4
8.0
48.4
9.8
10.0
62.0
13.1
Grundfos submersible pump motors - 60 Hz
4-inch, single phase, 3-wire motors
Amperage
Full
Lock
S.F.
load
rotor
amps
4.5
21.5
6.0
6.9
31.4
8.4
8.0
38.0
9.8
9.4
45.9
11.6
9.2 Guide for engine-driven generators
in submersible pump applications
Minimum kilowatt rating of
generator for three-wire
submersible pump motors
Motor
[hp]
Externally
regulated
0.33
0.5
0.75
1
1.5
Notes:
Table is based on typical 176 °F (80 °C) rise
continuous duty generators with
35 % maximum voltage dip during start-up
of single-phase motors.
Contact the manufacturer of the generator to
assure the unit has adequate capacity to run
the submersible motor.
If the generator rating is in KVA instead of
kilowatts, multiply the above ratings by 1.25
to obtain KVA.
Line-to-line
Full load
resistance
[ohms]
Blk.-Yel.
Power
Eff.
factor
Delta
62.0
76.0
5.2 - 6.3
62.0
75.0
3.2 - 3.8
63.0
82.0
2.5 - 3.1
64.0
85.0
1.9 - 2.3
Line-to-line
Full load
resistance
[ohms]
Blk.-Yel.
Power
Eff.
factor
Delta
62.0
76.0
4.7 - 5.7
62.0
75.0
3.2 - 3.9
63.0
82.0
2.6 - 3.1
69.0
89.0
1.9 - 2.3
[kW]
Internally
regulated
1.5
1.2
2.0
1.5
3.0
2.0
4.0
2.5
5.0
3.0
KVA
Max.
code
thrust
Red-Yel.
**
(lbs)
R
770
N
770
M
770
L
770
KVA
Max.
code
thrust
Red-Yel.
**
(lbs)
15.8 - 19.6
L
770
14 - 17.2
L
770
10.3 - 12.5
K
770
7.8 - 9.6
H
770
13