Installation

6.7.5 To connect the electrical wiring on the outdoor unit

Installer reference guide
44
Component
Recommended circuit breaker
Earth leakage circuit breaker
(a)
Electrical equipment complying with EN/IEC 61000-3-12 (European/International
Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current >16 A and
≤75 A per phase).
1 Remove the switch box cover.
2 Strip insulation (20 mm) from the wires.
a
a
Strip wire end to this point
b
An excessive strip length may cause electrical shock or leakage
3 Open the wire clamp.
4 Connect the interconnection cable and power supply as follows:
a
a
Interconnection cable
b
Power supply cable
c
Circuit breaker
d
Earth leakage circuit breaker
e
Power supply
RXM71N
RXP50~71M
RXF50+60B
RXF71A
ARXF50~71A
ARXM60+71N
RXM60N
ARXM50N
RXM42+50N
RXA42+50B
RXJ50N
MUST comply with applicable legislation
2
1
1
b
50 Hz
c
d
220-240 V
b
e
f
ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B +
RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B +
(a)
20 A
16 A
13 A
ARXF50~71A2V1B
R32 split series
4P513661-7H – 2019.12