5
|
Preparation
Installer reference guide
22
b
a
Baffle plate
b
Prevailing wind direction
c
Air outlet
Do NOT install the unit in the following places:
Sound sensitive areas (e.g. near a bedroom), so that the operation noise will
cause no trouble.
Note: If the sound is measured under actual installation conditions, the
measured value might be higher than the sound pressure level mentioned in
Sound spectrum in the data book due to environmental noise and sound
reflections.
INFORMATION
The sound pressure level is less than 70 dBA.
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may
shorten the life of the unit:
Where the voltage fluctuates a lot
In vehicles or vessels
Where acidic or alkaline vapour is present
Seaside installation. Make sure the outdoor unit is NOT directly exposed to sea
winds. This is to prevent corrosion caused by high levels of salt in the air, which
might shorten the life of the unit.
Install the outdoor unit away from direct sea winds.
Example: Behind the building.
a
If the outdoor unit is exposed to direct sea winds, install a windbreaker.
Height of windbreaker≥1.5×height of outdoor unit
Mind the service space requirements when installing the windbreaker.
b
a
b
c
ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B +
RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B +
ARXF50~71A2V1B
R32 split series