4.5 Completion Status

The completion statuses that DN311 returns in response to the requests issued by the S
controller are shown below.
Except for normal completion, an error code and the local node address are alternately
indicated by the 7-segment LED on the front panel of the DN311.
The error code indication stops when the following request is completed normally.
Completion status
Normal completion
Local station failure 00A0H
Serial number
unregistered
Local station
parameters not set
yet
Length error
Station mode error
Transmission
inhibited
Format error
Component data
error
Memory pool
acquisition error
6F8C0903
Table 4-18 List of Completion Statuses
Code
0001H
Indicates a request is completed normally.
When a request for inhibited processing is issued in down
mode
A serial number registered in the DN311 disappeared → Ask
00A1H
for repair because the DN311 needs resetting.
00A2H
A request for inhibited processing is issued when local station
parameters have not been set yet.
00A3H
Data size of a bit strobe output data write request is 8 bytes or
more.
00A4H
A request for inhibited processing is issued during run mode; a
request for inhibited processing is issued during standby
mode.
00A5H
Reserved
00A6H
A request related to transmission is issued by the S controller
in a state where transmission is inhibited.
00B0H
Requested processing code is not supported
00B1H
Inhibited status is demanded by control request
00B2H
Requested year is invalid at time setting
00B3H
Requested month is incorrect at time setting
00B4H
Request day is incorrect at time setting
00B5H
Request hour is incorrect at time setting
00B6H
Request minute is incorrect at time setting
00B7H
Request second is incorrect at time setting
00B8H
Incorrect node address (other than 0 to 63) is set in response
to parameter setting request and explicit message request.
00C0H
Incorrect data is in the data constituting parameter setting
request. (See trace information for details.)
00C1H
Slave device input/output data cannot be allocated to the input/
output data area (when control request RUN is issued).
00C2H
The OS in the DN311 has failed to secure memory. Switch
power off and back on to reset the module.