Melink Intelli-Hood Controls Reference Manual page 40

Advertisement

POWER IN
(From Lighting Circuit)
120/230 v
Neutral
Terminal
Purpose
1
Alarm #1 Common
2
Alarm #1 24VDC Out
3
Sheild
4
Alarm #2 24VDC Out
5
Alarm #2 Common
6
Kitchen Temperature
7
Kitchen Temperature
8
Sheild
9
Supply Temperature
10
Supply Temperature
Input/Output Board
VOLTAGE SELECT
115
115 / 230
INPUT
L N G
Ground
Reference
Connections for 24VDC
Alarm #1 Output
Shield for 24VDC Outputs
Connections for 24VDC
Alarm #2 Output
Connections for Kitchen
Temperature Sensor
Temperature Sensor Sheild
Connections for Supply
Temperature Sensor
24 vdc Com
Relay Coil Sink
Aux Out 0-10vdc
Aux Out Com
Aux Out 4-20 ma
Shield
Aux In Com
Aux In 4-20 ma
Relay Input Dry
Relay Input Dry
Sup Temp Sens
Sup Temp Sens
Shield
Kitchen Temp
Kitchen Temp
Alarm #2 Out Com
Alarm #2 Out +24 vdc
Shield
Alarm #1 Out Com
Alarm #1 Out +24vdc
RESET
POWER
115 / 230 (15a)
LIGHTS
G
N
L
POWER OUT
(To Lights)
120/230 v
Neutral
Ground
Terminal
11
Relay Input
12
Relay Input
13
Auxiliary 4-20mA Input
14
Auxiliary 4-20mA Common
15
Sheild
16
Auxiliary 4-20mA Out
17
Auxiliary Out Common
18
Auxiliary 0-10VDCOut
19
Relay Coil Sink
20
24VDC Common
3-12
AUXILIARY INPUTS
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Purpose
Connections for External Relay
Input
External Speed Reference Signals -
Follows System Menu Setting #2
Auxiliary 4-20 mA Sheild
Auxiliary Speed Reference Signals -
Follows System Menu Setting #1
Not Used in Current Configuration
Reference