Siemens SINAMICS G120P Manual page 10

Pump control with timer
Hide thumbs Also See for SINAMICS G120P:
Table of Contents

Advertisement

2 Engineering
Figure 2-3
Voltage
p0304
Frequency
p0310
The following table shows the parameters of the quick commissioning.
Table 2-4: Parameters for entering motor data
Step
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Pump with SINAMICS G120P
Entry-ID: 109759888,
V1.0.1,
: Nameplate of a standard asynchronous motor
Power
Current
factor
p0305
p0308
Power
p0307
Parameters
p0096
Enter the value 1 for "Standard Drive Control" in parameter
p0096 (application classes).
p0100
Parameter p0100 defines the motor standard.
0: IEC motor (50 Hz)
1: NEMA-Motor (60 Hz)
p0210
Enter the device connection voltage in parameter p0210.
p0300
In parameter p0300 you select the type of motor:
1: Asynchronous motor
p0304
Entry of the rated voltage from the motor nameplate.
p0305
Entry of the rated current from the motor nameplate.
p0307
Entry of the rated power from the motor nameplate.
p0308
Entry of the power factor (cos
p0310
Entry of the rated frequency (in Hz) from the motor
nameplate.
p0311
Entry of the rated speed from the motor nameplate.
p0335
Entry of the engine cooling type:
0: self-cooling
1: forced cooling
2: liquid cooling
128: no fans
09/2019
Speed
p0311
Description
) from the motor nameplate.