11. Operation (continued)
Parameter #
Description
bt
Boiler Temperature
SP
Boiler water set point
HL
High Limit Set point
HdF
High Limit Differential
tt
Heat Request Status Shown as either ON or OFF. Indicates whether there is a call for heat.
DHW Request
dh
Status
FLA
Flame Current
run
Run Time Hours
CyC
Boiler Cycles
Err
Error Number
Status # Description
HL
dF
Or
PP
St
Pt
dh
rst
F-C
bAc
40
Table 11.5: Operating Mode Parameters
Meaning
Current boiler water temperature measured by the control's sensor.
Current target temperature (always the same as the high limit setting un-
less Crown outdoor reset card option is installed).
Boiler will stop firing if boiler water temperature exceeds this value
(Circulator/s will continue to operate)
If high limit setting is reached, boiler water temperature will need to drop
by this amount before boiler will again fire during the same call for heat.
Shown as either ON or OFF. Indicates whether there is a call for domestic
hot water (DHW). Note that if the dh zone on the S9361A is used as a
second heating zone (see Table 12.6), this parameter will be shown as
OFF and tt will be shown as ON when this zone calls for heat.
Flame rectification signal (uA)
Total amount of time gas valve has been open (burner firing) since control
was new (hours, starting from 1).
Total number of burner cycles on the control
Present only if the control has detected a problem. See Table
list of error codes and suggested corrections.
Table 11.6: Adjustment Mode Parameters
High Limit Set point
High Limit Differential
Circulator overrun
Thermal Purge time
Thermal Purge Start Temp
DHW Priority
Use of Second Zone
Reset
Temperature Units
Exit Adj. mode
Factory
Setting
Permissible Range
180F
140-220F
15F
10-30F
0 min
0-10 minutes
2 min
2-20 minutes
140F
140-180F
ON
ON or OFF
dh (dhw)
dh
or
tt2 (2nd heating zone).
OFF or
N/A
Momentary ON
F
F or C
N/A
N/A
13.0