Crown Boiler BWF Series Installation Instructions Manual page 39

Gas-fired induced draft hot water boiler
Table of Contents

Advertisement

11. Operation (continued)
Status # Description
1
Standby
Waiting for Pressure
2
Switch to open
Waiting for Pressure
3
Switch to close
4
Prepurge
6
Spark
7
Flame proving
8
Running
10
Retry/Recycle Delay
Pressure Switch failed to
11
open.
Pressure Switch failed to
12
close.
13
Soft Lockout
14
Hard Lockout
15
Waiting for limit to close
Flame Present out of
16
Sequence
17
Self test
Note:
In operating mode, holding either the ↑ or ↓ button while viewing a given parameter will keep
the display on the actual reading. For example, pressing ↑ while reading boiler temperature as
shown in Figure 11.4 will keep the display on 180 for as long as the button is held. This makes it
easier to view readings "live" if they are changing rapidly.
109836-01 - 04/20
Table 11.3: Status Codes
Meaning
No call for heat or DHW
OR
Call for heat present , but boiler is in thermal purge (See
OR
Call for heat/DHW present but boiler temperature is above high limit (HL) set-
ting.
Control is confirming that air pressure switch contacts are open before starting
fan.
Fan is on and control is waiting for air pressure switch contacts to close.
Pressure switch is closed and control is waiting 30s before starting trial for
ignition.
Control is attempting to light pilot
Control is verifying that the pilot flame is on and stable.
Main burner is on
Control was unable to establish pilot and is waiting 60 seconds before trying
again
OR
Proof of pilot was lost after pilot was established and control is waiting 60 sec-
onds before attempting to relight.
Control waited in Status #2 for 60 seconds and air pressure switch remained
closed. Boiler will remain in this state until the air pressure switch opens.
Control waited in Status #3 for 60 seconds and air pressure switch failed to
close. Boiler will remain in this state until the air pressure switch closes.
A fault is preventing the boiler from firing. Boiler will be allowed to fire after
problem clears itself AND a forced delay period has passed.
A fault has occurred which requires manual intervention before the boiler will
again operate. This intervention can be in the form of interruption of the power
supply to the boiler or resetting the control in Adjustment mode.
LWCO open, limit jumper plug missing, or flame rollout switch open
A flame was detected when none should have been present.
Boiler was just energized and control is running a self check.
1 sec. 

Figure 11.4: Typical Operating Mode Display (Boiler Temp Shown)
1 sec.
1 sec.

PP
on page 40)

 
39