6. Vent System Design (continued)
'Y'
'X'
Max. Overhang
0 - 12"
NOT PERMITTED
12 - 48"
17 - 29"
X minus 7"
Greater than 48"
17 - 29"
36"
Note: Overhang may not be ventilated if 'Y' is less than 48"
Figure 6.9c: Location of Vent Terminal Under Overhangs
18
109836-01 - 04/20