All carriers must be earthed. Each carrier has a surge-ground screw, located to the rear of
the alarm module – see Figure 4.4 below.
This terminal is used to carry the surge current to ground if surge protection modules are
used on the carrier. In these circumstances, it MUST be connected via a low impedance
path to the plant ground. It is recommended that a cable with a cross-sectional area of
at least 4mm
grounding bus.