i) It is recommend to use negatively grounded inverters to avoid the PID effect for non-PID free modules.
j) If modules are connected in series, the total voltage is equal to the sum of individual voltages. The
recommended as below,
System voltage≥N*Voc[1+TCVoc* (Tmin-25)]
Where
N
module numbers in series
Voc
Open circuit voltage (refer to product label or data sheet)
TCVoc
Temperature coefficient of open circuit voltage (refer to product label or data sheet)
Tmin
Minimum ambient temperature

4. Maintenance and Care

It is required to perform regular inspection and maintenance of the modules, especially during the warranty
period. To ensure optimum module performance, Jinko recommends the following maintenance measures:

4.1 Visual Inspection

Inspect the modules visually to find if there are any visual defects, If there are, the following items should be
evaluated:
a) If modules are observed having slight cell color differences at different angles, this is a normal
phenomenon of modules with anti-reflection coating technology.
b) Whether the glass is broken.
c) No sharp objects are in contact with the PV module surfaces.
d) PV modules are not shaded by unwanted obstacles and; or foreign material.
e) Corrosion along the cells' bus-bar. The corrosion is caused by moisture intrusion thought the module
back sheet. Check the back sheet for damage.
f) Check whether the back sheet is burn out.
g) Check if screws and mounting brackets are tight, adjust and tighten as necessary.