Third Party Racks With Vertical Pdus - Rpq Required - Dell EMC VMAX3 Series Site Planning Manual

Table of Contents

Advertisement

Third party racks with vertical PDUs — RPQ Required
Each system bay is powered by two redundant power distribution units (PDUs), one PDU for each
power zone. Rather than use the standard Dell EMC horizontal PDU, the customer can use vertical
PDUs via RPQ. The general requirements for third party racks with rear-facing or inward-facing
PDUs are listed below.
l
l
General requirements for vertical PDUs within third party racks
In addition to meeting standard VMAX array power requirements, vertical PDUs should abide by
the following:
l
l
l
If the customer requires power to be supplied from overhead, Dell EMC recommends one of the
following:
l
l
The cables should be dressed to allow all doors to open freely, minimize cable congestion, and
provide access to components within the system.
Requirements for third party racks with vertical PDUs (inward-facing)
Requirements for third party racks with vertical PDUs (rear-facing)
Both PDUs support AC-line input connectivity and provide outlets for every component in the
bay.
The PDU must be available in the wiring configuration that matches the customer power
supply.
Options include:
Single-phase
n
Three-phase Delta
n
Three-phase Wye
n
Each PDU should meet the following requirements:
At a minimum, a total of 24 power outlets must be provided.
n
The outlets are divided into six banks with each bank consisting of four IEC 60320 C13
individual AC outlets.
Each bank of outlets is connected to individual branch circuits that are protected by a
n
single two pole 20 Amp circuit breaker.
The PDU capacity should exceed the power requirements shown in the Power Calculator
n
for the specific max configuration.
Single PDU mounted per side per
n
Option 1: Replace the rear top cover of the bay with the ceiling routing top cover, described in
Overhead routing kit
on page 84, which allows the power cables inside the machine to be
routed out through the top.
Option 2: "Drop" the power cables down the hinge side, to the bottom, and route them inside
the machine.
Dell EMC
VMAX3
Family Site Planning Guide VMAX 100K, VMAX 200K, and VMAX 400K
Figure 28
on page 78 and
Third Party Racking Option
on page 80
on page 78
Figure 29
on page 80.