6.4 DESCRIPTION OF THE MICROPROCESSOR'S FUNCTIONS
WARNING - CAUTION
Do not interact with the functions that are not described n this
manual. They are for the specialized Engineer only with password
insertion).
The only functions with which the expert Operator can interact re
described below.

6.5 SETTING THE CHILLED WATER TEMPERATURE (SET-POINT)

3. Press 8 key to set the chilled water temperature set-point "xK1".
4. Decrease the water temperature by pressing 7 key , or increase it by
5. Store the set value by pressing 8 key. Automatically the cursor
6.
RC GROUP S.p.A I_TRP_0909_GB
Setting of the chilled / hot / domestic water set-point temperature
-
(see § 6.5).
Alarm signals (see § 6.6).
-
Displaying alarms list (see § 6.7).
-
Displaying of the hour-meter and maintenance alarm (see § 6.8).
-
Date and time setting (see § 6.9).
-
Setpoint xK1
07.0°C
Setpoint xK3
45.0°C
Setpoint xK4
40.0°C
pressing 6 key. The keys must be held down until the desired
temperature is reached.
moves to the second value (Setpoint xK3 for hot water). Repeat the
sequence as previous described.
Set now the third value (Setpoint xK4 for domestic water).
Interrupt the display by pressing 4 key.
Chapter 6 - INFORMATION FOR USE
1. Press 5 key to access to the main
control functions menu.
2. Press 7 key up to SET-POINT is
displayed".