Unibox T
3.6 Technical data
Max. operat-
100°C
ing tempera-
ture t s
Max. operat-
10 bar
ing pressure
p s
Max. differen-
1 bar
tial pressure
Installation
57 mm
depth
Control piston
M30x1.5
connection
thread
Fluid
Water, mixtures of water
and glycol
4.
Accessories and spare
parts
Spare parts and accessories are available from
specialist stores.
The following items are available as accesso-
ries:
Designation
Cover
Plastic white
Genuine glass
white
Genuine glass
black
Fixing channel
Pipe conduit unit
Duo connection piece
Protective tube (see illustIllust.
6 on page 24)
102272280-V01.02.2020
The flow tempera-
ture of the surface
heating system
must not exceed
55 °C (low tempera-
ture heating).
Item no.
1022776
1022774
1022775
1022652
1022653
1022650
1022655
1501184
Accessories and spare parts
5.
Transport and storage
Transport the product in its original packaging.
Store the product under the following condi-
tions:
Temperature
-20°C to +60°C
range
Relative air
Max. 95%
humidity
Particles
Store dry and free from
dust
Mechanical
Protected from mechani-
influences
cal agitation
Radiation
Protected from UV rays
and direct sunlight
Chemical
Do not store together
influences
with solvents, chemicals,
acids, fuels or similar
substances
6.
Installation
6.1 General installation advice
Note the following prior to installation:
• The lower edge of the "Unibox T" must be
at least 20 cm above the finished floor.
• The front face of the "Unibox T" must be
level with the finished wall.
Should the wall not have been
finished, take the plaster and tile
thickness into account.
• The opening of the wall box unit must face
downwards.
• The thermostat must not be influenced by
other heat sources.
• Use the enclosed brackets to align and fix
the "Unibox T".
23