Hydran* 201i Instruction Manual
5.5.6.5
Force Host Call
This function is used to perform two actions:
• To initialize the modem in the H201Ci Controller with the communication rate
selected using the BaudRate parameter.
• To test the communications between the Hydran 201Ti and the Hydran Host
software by forcing the H201Ci Controller's modem to call the modem of the host
computer where the Hydran Host is running.
Note: In the versions 2.1 and prior of the H201Ti embedded software, in the Call
OnAlarm mode, the telephone number set in the modem's register 0 is dialed
automatically at midnight. This function does not exist in version 2.2.
5.5.6.6
H201Ti ID and PowerStation ID
The H201Ti ID parameter is used to set the Hydran 201Ti's identification number. An
exclusive identification number must be assigned to each H201Ti in a local network.
The PowerStat ID parameter is used to set the power station's identification number.
The same power station identification number must be assigned to all H201Ti's in a local
network, but each local network must have a different power station identification
number.
The default values of the H201Ti ID and PowerStat. ID parameters are therefore
usually modified. Furthermore, the H201Ti and power station's identification numbers
must correspond to those assigned to the same H201Ti's and power station in the
Hydran Host or Perception software.
CAUTION
Note:
The identification number of each H201Ti must be recorded during the
configuration of the local network.
5.5.6.7
MODBUS Address
This function is used to select the Modbus address and must be set to a numeric
value between 1 and 255.
This setting is relevant and shall be properly configured only when the Comm
Channel and Default Channel are set to LocalUSB ModBus or SupervLnk MODBUS. Else,
when 201Ti is set to Hydran protocol (Comm Channel and Default Channel are Local USB
or Supervisory Link), this setting is ignored.

5.5.7 Relays/Analog Submenu (Extended Menu Only)

The Relays/Analog submenu is used to:
MA-033
Rev. 14.0, 12-Nov-18
The identification number of at least one H201Ti in a local
network must be set between 1 and 5 (inclusively).
Page 75