CHAPTER 3: INSTALLING THE G500
Inrush current
Reverse polarity
protection
Overcurrent
protection
Overvoltage
protection

Power-On Self-Test (POST)

Super Capacitor

G500 system redundancy

G500 SUBSTATION GATEWAY INSTRUCTION MANUAL
The inrush current is typically 13A when powering up.
The product is equipped with built-in reverse polarity protection. If + and - are swapped the
unit will not power-up and harm to neither the power supply nor the unit will occur.
The overcurrent protection function interrupts an uncontrolled fault current or overcurrent
before serious damage can occur, such as overheating of the equipment.
The PSU included fuse is rated for 16A continuous current. If that current is exceeded by
factor 10 the fuse will blow in between 10ms and 100ms.
The fuse is placed in"-"connection of the power supply.
The fuse is soldered directly onto the product. There is no fuse holder. The fuse should only
be replaced by GE personnel.
The voltage to the inner loads is protected by a varistor. High increase of the voltage will
cause the internal current fuse to blow and/or the Varistor to break.
The varistor is soldered directly onto the product. There is no fuse holder. The varistor
should only be replaced by GE personnel.
Each time the G500 boots up it must pass the POST (Power-On Self-Test). The following
tests make up the POST:
CPU must exit the reset status and be able to execute instructions
SPI Flash ROM and NVRAM is accessible
Checksum must be valid
CMOS is readable, CMOS checksum must be valid
CPU must be able to access all forms of memory such as the memory controller,
memory bus, and memory module
The first 64 KB of memory must be operational and must be capable of holding the
POST code
I/O bus / controller must be accessible
I/O bus must be able to write / read from the video subsystem and be able to access
all video RAM
If the G500 does not pass one or more of the above tests, the board will fail the POST and
display a hexadecimal value on the lower right corner of the screen. Please contact GE's
Grid Solution support with the hexadecimal code in this case.
The G500 does not include a battery. The real-time clock is buffered via a super capacitor
for at least 7 days of no connection to power. After this time, it may be reset to 12:00 AM,
01-10-2000 at start-up and therefore necessary to readjust the system time.
A redundant G500 setup allows a secondary G500 to automatically take over operations
from a paired G500 unit that has failed.