CHAPTER 3: INSTALLING THE G500
The varistor is soldered directly on the product. There is no fuse holder. The varistor should
only be replaced by GE personnel.

Low Voltage Power Supply

The Low Voltage Power Supply only handles DC input, with DC input voltage from 20 to
54V. The PSU tolerates a 10% variation in these values (18 to 60V).
The PSU has a maximum current consumption of 10.2A.
Connect the "+" and "-"wires according to the following figure. The GND wire is optional.
Wires
The conductor size is from 16 AWG to 12 AWG and Strip Length is 7mm.
After plugging cable lines into the mating connector, plug the mating connector to the
product and secure the plug with the two screws.
Breaker circuit
A 20A IEC/USA/Canada breaker circuit is required as pre fuse.
Disconnect device
A readily accessible disconnect device shall be incorporated external to the unit.
26
GE INFORMATION
G500 SUBSTATION GATEWAY INSTRUCTION MANUAL