Cable Sizes; Ec Declaration Of Conformity; Serial Numbers - SDMO PERFORM 3000 Instruction And Maintenance Manual

Hide thumbs Also See for PERFORM 3000:
Table of Contents

Advertisement

Available languages

Available languages

11. Cable sizes

Laying mode = cables on cable tray or racks not perforated / admissible voltage drop = 5% / Multiconductors.
Cable type PVC 70°C (example H07RNF) / Ambient temperature =30°C.
Rated Current (A)
Single-phase
10
16
20
25
32
40
50
63

12. EC Declaration of conformity

Name and address of manufacturer: SDMO Industries, 12 bis rue de la Villeneuve, CS 92848, 29228 BREST CEDEX 2, FRANCE.
Description of the equipment
Make
Type
Name and address of the person authorised to create and keep the technical file
G. Le Gall, SDMO, 12 bis rue de la Villeneuve, CS 92848, 29228 BREST CEDEX 2, FRANCE
G. Le Gall, the manufacturer's authorised representative, hereby declares that the product conforms to the following EU Directives:
2006/42/EC / Machinery Directive.
2006/95/EC / Low Voltage Directive.
2004/108/EC / Directive on Electromagnetic Compatibility.
2000/14/EC / Directive relating to the Noise Emission of Outdoor
Equipment.

13. Serial numbers

Serial numbers shall be requested for technical assistance or when ordering spare parts.
Please indicate the generating set and engine numbers below.
Generating set serial number:
(E.g. "No.: 45/2007 – 39645109 – 001")
(indicated on the identification plate of the generating set affixed inside one of the two bands or to the frame.)
...............................................
Engine brand:
Engine serial number:
(E.g. Kohler "SERIAL NO. 4001200908")
0 to 50m
mm² / AWG
Three-phase
4 / 10
1.5 / 14
6 / 9
2.5 / 12
10 / 7
2.5 / 12
10 / 7
4 / 10
10 / 7
16 / 5
16 / 5
25 / 3
Generating set
SDMO
PERFORM 3000, PERF3000
PERFORM 3000 GPL
3499231090015
......../.............. - ........................ - .........
...............................................
Cable lengths
51 to 100m
mm² / AWG
Single-phase
Three-phase
10 / 7
2.5 / 12
10 / 7
4 / 10
16 / 5
4 / 10
16 / 5
6 / 9
25 / 3
35 / 2
35 / 2
50 / 0
For the directive 2000/14/EC
Notified body:
CETIM
F60304 – SENLIS.
BP 67
Compliance procedure: Appendix VI.
Sound power level guaranteed (LwA): 96 dB(A).
Rated output: 2400 W
101 to 150m
mm² / AWG
Single-phase
Three-phase
10 / 7
16 / 5
25 / 3
25 / 3
35 / 2
50 / 0
50 / 0
70 / 2 / 0
05/2011 - G. Le Gall
4 / 10
6 / 9
6 / 9
10 / 7