38 kv type simple electrical ground & test device (seg&td) upper terminal
Hide thumbs Also See for VCP-WHD:

Advertisement

38 kV Type VCP-WHD Simple Electrical
Ground & Test Device (SEG&TD) upper
terminal instruction booklet
6.
On the remote operator, depress the "Open" and "Permit" but-
tons simultaneously until the 38 kV SEG&TD is opened.
7 .
Return the selector switch to the "Off" position.
8.
Unplug the remote operator connector from the receptacle on
the front of the 38 kV SEG&TD.
9.
Rotate key "KU" in Lock #1 and remove it. This electrically dis-
ables the SEG&TD.
10. Place key "KU" in the Utility lockbox.
3.7
Removing the SEG&TD from breaker cell
1.
Verify the 38 kV SEG&TD is in the open position.
2.
Remove key "KU" from the Utility lockbox and insert it into
Lock #1.
3.
Rotate key 'KU' in Lock #1 and remove key "KB" . This electri-
cally disables the 38 kV SEG&TD.
4.
Insert key "KB" into Lock #2 and rotate then remove key "KC"'.
5.
Using the slide handles, withdraw the 38 kV SEG&TD to the
disconnected position.
Figure 51. Slide handles.
6.
Once the 38 kV SEG&TD is in the disconnected position, insert
key "KC" into Lock #3 and rotate allowing the SEG&TD to be
removed from the breaker cell.
7 .
Remove the 38 kV SEG&TD from the switchgear compartment.
8.
Rotate key "KC" in Lock #3 and remove it.
9.
Insert key "KC" into Lock #2 and rotate it to release key "KB" .
10. Insert key "KB" into Lock #1 then rotate and remove key "KU" .
11. Return key "KU" to the Utility lockbox.
12. Store the 38 kV SEG&TD in an environment that meets specifi-
cations.
N
otee:
The 38 kV SEG&TD should be in the open position with the test port
shutters locked closed and keys held captive as detailed in Table 2.
Slide handles

4 Maintenance

The 38 kV SEG&TD is very similar to the VCPW-HD/HDR Vacuum
Circuit Breaker. For maintenance information for the 38 kV
SEG&TD, please refer to the "Instructions for the Use, Operation,
and Maintenance of Type VCPW-HD/HDR Vacuum Circuit Breakers"
instruction manual (IB131011EN) supplied with the breaker.