38 kv type simple electrical ground & test device (seg&td) upper terminal
Hide thumbs Also See for VCP-WHD:

Advertisement

38 kV Type VCP-WHD Simple Electrical
Ground & Test Device (SEG&TD) upper
terminal instruction booklet
Figure 34. Selector switch in the "Off" position.
12. Plug in the remote operator to the receptacle in the front of the
38 kV SEG&TD.
Figure 35. Remote operator connected to the remote operator
receptacle.
13. Rotate the selector switch to the "Close" position.
Remote operator
receptacle
Figure 36. Remote operator plugged into its receptacle and the
selector switch in the "Close" position.
14. On the remote operator, depress the "Permit" and "Charge/
Close" buttons simultaneously until the 38 kV SEG&TD is
closed (the incoming feeder is grounded).
Figure 37. Depressing the "Permit" and "Charge/Close" buttons
on the remote operator.
15. Insert key "KU" into Lock #1 and rotate to release key "KB" .
This electrically disables the 38 kV SEG&TD.
16. Insert key "KB" into Lock #4 and rotate key "KD" to release it.
This mechanically locks the 38 kV SEG&TD in the "Close" con-
dition.