Testing Illuminated Warning Panel; Checking All Fire Detectors - Siemens XC1003-A Operation

Extinguishing control unit
Table of Contents

Advertisement

6.3

Testing illuminated warning panel

6.4

Checking all fire detectors

Building Technologies
Fire Safety & Security Products
Check the illuminated warning panel for correct function.
Proceed as follows:
1. Enable "Access level 2".
The LED "Operating access" lights up.
2. Press and hold the key "Digit 4" and press the "Lamp test" key:
The illuminated warning panel is activated for 30 seconds.
3. Press the "Silence Re-sound Horn" or the "Lamp test" key:
The illuminated warning panel is de-activated before 30 seconds elapse.
Check all fire detectors annually. This way you are ensuring the serviceability of
the extinguishing system.
Here's how to check the fire detectors:
1. Enable "Access level 2".
The LED "Operating access" lights up.
2. Press the "ZONES det. test/enable" until the yellow LED is lit (slow flashing) at
the desired detector zone.
The first pressing sets detector zone 1 to "Detector test":
The yellow LEDs "Detector Zone 1"/"Detector test"/"Disabled"/"Manual
only" light up.
The second pressing sets detector zone 2 to "Detector test":
The yellow LEDs "Detector Zone 2"/"Detector test"/"Disabled"/"Manual
only" light up.
The third pressing sets detector zones 1 and 2 to "Detector test":
The yellow LEDs "Detector Zone 1 and 2"/"Detector test"/"Disabled"/
"Manual only" light up.
The fourth pressing sets detector zone 3 to "Detector test":
The yellow LEDs "Detector Zone 3"/"Detector test"/"Disabled" light up.
The yellow LED "Manual only" is no longer lit (depending on programming).
The fifth pressing sets detector zones 1, 2 and 3 to "Detector test":
The yellow LEDs "Detector Zone 1 to 3"/"Detector test"/"Disabled"/"Manual
only" light up.
The sixth pressing sets the "Manual release (Zone 4)" to "Detector test":
The yellow LEDs "Detector Zone 4"/"Detector test"/"Disabled" light up.
The yellow LED "Manual only" is no longer lit.
The seventh pressing sets all detector zones to "Detector test":
The yellow LEDs of "Zones 1 to 4"/"Detector test"/"Disabled"/"Autom. &
Man. blocked" light up.
The eighth pressing re-enables all detector zones:
The yellow LEDs of "Zones 1 to 4"/"Detector test"/"Disabled"/"Autom. &
Man. blocked" are no longer lit.
3. The system is again in normal operating mode.
Note:
Sequentially trigger an alarm on all detectors of the zone. The red zone LED at the
control unit and the alarm indicator at the detector light up for approx. 10 seconds.
No acoustic alarm is initiated
Maintenance
23
A6V10099835_a_en
12.2007