Checking The Remote Transmission Of Alarm - Siemens XC1003-A Operation

Extinguishing control unit
Table of Contents

Advertisement

Maintenance
6.5

Checking the remote transmission of alarm

24
Building Technologies
Fire Safety & Security Products
If you must periodically check -on a weekly basis, for example the "Remote
transmission of alarm (RT-alarm)", you can simulate the enabling of manual
release. When doing this, however, exercise extreme caution: first of all, always
block the automatic and manual activation of extinguishing as well as the alarm
horn and disable the fire control.
Before checking the remote transmission, ensure that activation of extinguishing
WARNING
is in fact blocked, the alarm horn and the controls are disabled and the receiving
station is notified of the immanent test.
Disable extinguishing, alarm horn and fire controls
1. Enable "Access level 2":
The LED "Operating access" lights up.
2. Press the "Mode select" key twice:
The LED "Autom. & Manual blocked" lights up.
3. Press the "Enable/Disable" key ("Horn/actuator"/"Fire control") three times:
The LEDs "Horn/Actuator" and "Fire control" light up.
Simulate state "Released" at the pressure switch
1. Activate manually the pressure switch in order to initiate state "Released".
2. Check whether state "Released" and "Remote transmission" is indicated:
Alarm horn and Fire control are not activated.
The red LEDs "Released" and "Remote transmission" are lit.
3. Check whether remote signal is received at the receiving station.
4. Restore the pressure switch, if mechanically locked, and reset system.
A6V10099835_a_en
12.2007