3.7 Adjusting the dosing flow via the stroke length

Make sure the pump was installed and started up correctly.
To increase the dosing flow, turn the adjusting knob slowly to the left.
To decrease the dosing flow, turn the adjusting knob slowly to the right.
Related information
• 3.2 Safety instructions and requirements for startup
• 5.1.1 DMX 221 components
• 5.1.2 Functional principle of the pump
• 9.6 Dosing curves

3.8 Adjustment of the stroke rate with a frequency converter

If a frequency converter is connected, the dosing flow can be adjusted by changing the stroke
rate. This can only be done in the range of 10-100 % of the maximum stroke rate.
For more information, read the installation and operating instructions of the frequency converter.
Related information
• 11.2 Pumps with VFD

3.9 Opening and reactivating the integral relief valve

Make sure the pump was installed and started up correctly.
Make sure the pump is running during this task.
A
Fig. 3.9-1 Knob positions
1. To open the relief valve, turn the relief-valve knob to position B.
The relief valve is open. Dosing medium and air can flow out through the overflow line.
2. To reactivate the relief valve, turn the relief-valve knob to position A.
The relief valve is reactivated and will open at the set opening pressure.
Related information
• 3.10 Setting the opening pressure of the integral relief valve
Only adjust the stroke length while the pump is running.
WARNING
Chemical hazard
Death or serious personal injury
● Wear protective clothing when working on the dosing head, connections or
lines.
● Collect and dispose of all chemicals in a way that is not harmful to persons or
the environment.