Figure 19 - Motor Details Screen - York YMC2 Operation And Maintenance

Centrifugal liquid chillers with r-134a or r-513a refrigerant
Hide thumbs Also See for YMC2:
Table of Contents

Advertisement

SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION

FIGURE 19 - MOTOR DETAILS SCREEN

OVERVIEW
This screen displays information pertinent to the Motor
Temperature Monitoring feature. The feature consists
of motor winding temperature and motor housing tem-
perature. Also, individual winding temperature sensors
can be disabled on this screen.
DISPLAY ONLY
Motor Run (LED)
Illuminates when the OptiView™ control center is
commanding the motor to run.
%Input Full Load Amps
Displays the input current as a percentage of chiller full
load amps.
Output Frequency
Displays the frequency at which the VSD is operating
the motor. This value is returned from the VSD Logic
Board.
58
MOTOR DETAILS SCREEN
VGD Position
Displays the present variable geometry diffuser posi-
tion as a value between 0% (closed) and 100% (full
open).
Motor Temperatures
Displays the enabled motor winding temperatures for
phase A, B and C. Individual temperatures can be dis-
abled using the TEMPERATURE DISABLE Setpoint.
The software prevents more than 2 of the 3 sensors at
either end of the motor to be disabled. When an in-
dividual temperature is disabled, the temperature data
box does not appear. Any input that registers as open
will display the minimum temperature 32°F.
Average Winding Temperature
This value is calculated as the average of all enabled
and valid motor winding temperatures. Any winding
temperature that registers as open, out of range or dis-
abled is not used in the calculation. A maximum of 6
temperatures is used to calculate the average.
FORM 160.84-OM1
ISSUE DATE: 9/21/2017
LD17934a