Deluge valve, diaphragm style, 1-1/2 thru 8 inch (dn40 thru dn200), deluge system - dry pilot actuation
Hide thumbs Also See for DV-5:

Advertisement

DV-5 Deluge Valve, Diaphragm Style,
1-1/2 thru 8 Inch (DN40 thru DN200),
Deluge System – Dry Pilot Actuation
General
Description
The DV-5 Deluge Valve (described in
Technical Data Sheet TFP1305) is a
diaphragm style valve that depends
upon water pressure in the Diaphragm
Chamber to hold the Diaphragm closed
against the water supply pressure.
When the DV-5 Valve is set for service,
the Diaphragm Chamber is pressurized
through the trim connections from the
inlet side of the system's main con-
trol valve, for example an O.S.&Y. gate
valve or butterfly valve (Ref. Figures 1
and 4).
Opening of a dry pilot sprinkler releas-
es pneumatic pressure from the pi-
lot line. In turn, the Dry Pilot Actuator
(Item D3 - Fig. 3A and 5) opens and
releases water from the Diaphragm
Chamber faster than it can be replen-
ished through the 1/8 inch (3,2 mm) re-
striction provided by the Model ASV-1
Automatic Shut-Off Valve in the dia-
phragm supply connections (Item 5 -
Fig. 3A and 5, also described in Tech-
nical Data Sheet TFP1384). This results
in a rapid pressure drop in the Dia-
phragm Chamber, and the force differ-
ential applied through the Diaphragm
that holds it in the set position is re-
duced below the valve trip point. The
water supply pressure then forces the
Diaphragm open permitting water to
flow into the system piping, as well as
through the Alarm Port to actuate the
system alarms.
As water flows into the system, the pi-
lot chamber of the Model ASV-1 Auto-
matic Shut-Off Valve (Item 5 - Fig. 3A
and 5) becomes pressurized and the
ASV-1 automatically shuts off the di-
aphragm chamber supply flow to the
DV-5 Diaphragm Chamber. Shutting
off the diaphragm chamber supply flow
prevents the DV-5 Diaphragm Chamber
from becoming re-pressurized, there-
Page 1 of 16
by preventing inadvertent closing of the
DV-5 during a fire (as may be the case
if an actuation device other than a pi-
lot sprinkler were to be closed after its
initial operation, e.g., a remote manual
control station).
NOTICE
The DV-5 Deluge Valve with Dry Pilot
Actuation Trim described herein must
be installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association, in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
JULY 2014
Worldwide
www.tyco-fire.com
Contacts
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
Contact the installing contractor or
manufacturer with any questions.
TFP1315

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DV-5 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco DV-5

  • Page 1 The owner is responsible for maintain- nical Data Sheet TFP1384). This results DV-5 during a fire (as may be the case ing their fire protection system and de- in a rapid pressure drop in the Dia- if an actuation device other than a pi- vices in proper operating condition.
  • Page 2 TFP1315 Page 2 of 16 Water Supply Pressure Gauge Water ow Pressure Alarm Switch DV-5 Deluge Valve (Shown at Rear of Valve) Main Control Valve (N.O.) Diaphragm Chamber Pressure Gauge Water Motor Alarm (Optional) Diaphragm Chamber Supply Control Valve (N.O.) System Drain Valve (N.C.)
  • Page 3 TFP1315 Page 3 of 16 DV-5 Deluge Valve Water Supply Pressure Gauge Water Motor Alarm (Optional) (Shown at Front of Valve) Main Control Valve (N.O.) Dry Pilot Actuator Diaphragm Chamber Pressure Diaphragm Chamber Supply Low Pressure Alarm Switch Gauge (Shown at Front of Valve) Control Valve (N.O.)
  • Page 4: Technical Data

    The trim arrangement is provided with exposed to freezing temperatures can for the DV-5 Valve and are necessary galvanized, black, or brass nipples and create an ice buildup that could pre- for its proper operation.
  • Page 5 Valve Port identi cation. 3/4" x 1-1/2" 3/4" x 2-1/2" Route all Tubing to Drip Funnel, Item 14. FIGURE 3A (1 OF 3) 1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DELUGE VALVES EXPLODED VIEW OF VERTICAL DRY PILOT ACTUATION TRIM...
  • Page 6 DV-5 DELUGE VALVE See Figure 2 of TFP1305 for SHOWN Valve Port identi cation. Route all Tubing to Drip Funnel, Item 15. FIGURE 3A (2 OF 3) 3 INCH (DN80) DV-5 DELUGE VALVE EXPLODED VIEW OF VERTICAL DRY PILOT ACTUATION TRIM...
  • Page 7 DV-5 DELUGE VALVE Valve Port identi cation. SHOWN Route all Tubing to Drip Funnel, Item 15. FIGURE 3A (3 OF 3) 4, 6, AND 8 INCH (DN100, DN150 AND DN200) DV-5 DELUGE VALVES EXPLODED VIEW OF VERTICAL DRY PILOT ACTUATION TRIM...
  • Page 8 TFP1315 Page 8 of 16 NOTES: Select Appropriate Nipple and Tube Sizes per DV-5 Deluge Valve Size Nipple Install subassemblies in alphabetical order. Number 1-1/2" (DN40) 2" (DN50) 3" (DN80) 4" (DN100) 6" (DN150) 8" (DN200) See Figure 2 of TFP1305 for Valve Port 1/2"...
  • Page 9: Left View

    MINIMUM CLEARANCE LEFT VIEW FRONT VIEW FIGURE 4 1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DELUGE VALVES VERTICAL DRY PILOT ACTUATION / NOMINAL INSTALLATION DIMENSIONS Materials of • Low pressure alarm setting at ap- Systems using a seawater or brackish...
  • Page 10: Installation

    Main Control Valve Tubing. Type L copper per ASTM B88. in order to facilitate setting of the DV-5 The DV-5 Valve must be installed in a Valve (Ref. Figure 4). readily visible and accessible location.
  • Page 11 6. Horizontal Arrangement uses only 7 out of 8 of Item 24, and 9 out of 10 of Item 33. Discard unused material. FIGURE 5 (1 OF 3) 1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DELUGE VALVES EXPLODED VIEW OF HORIZONTAL DRY PILOT ACTUATION TRIM...
  • Page 12 6. Horizontal Arrangement uses only 7 out of 8 of Item 25, and 12 out of 13 of Item 35. Discard unused material. (GREEN TINT) (ORDERED SEPARATELY) FIGURE 5 (2 OF 3) 3 INCH (DN80) DV-5 DELUGE VALVE EXPLODED VIEW OF HORIZONTAL DRY PILOT ACTUATION TRIM...
  • Page 13 8 of Item 25, and 2 out of 3 of Item 36. Discard unused material. FIGURE 5 (3 OF 3) 4, 6, AND 8 INCH (DN100, DN150, AND DN200) DV-5 DELUGE VALVES EXPLODED VIEW OF HORIZONTAL DRY PILOT ACTUATION TRIM...
  • Page 14: Care And Maintenance

    Drain Valve to verify that it is trol Valve. Close the Main Drain Valve dry pilot actuation system pressure of open and that the DV-5 Valve is com- as soon as water discharges from the 40 psi (2,8 bar). The Pressure Relief pletely drained.
  • Page 15 Step 7. Slowly open the Main Con- Proper operation of the DV-5 Valve (i.e., trol Valve. Close the Main Drain Valve opening of the DV-5 Valve as during a as soon as water discharges from the fire condition) must be verified at least drain connection.
  • Page 16 8 Inch G x G ....P/N 52-982-0-1AP GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 Copyright © 2014 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of the DuPont Corporation.

Table of Contents