6.5 User settings
The following table displays the options that can be changed by the user.
Submenu
Options on the display
Change
[English], [German] , [French],
language
[Spanish], [Russian]
If user select German for display
language,
Option item display as below:
[Englisch], [Deutsch], [Französisch],
[Spanisch], [Russisch]
User
[enabled<****>], [disabled]
password
Audible
[enabled], [disabled]
alarms
Set date and
mm/dd/yyyy; hh:mm
time
Relay
[UPS ok], [on bypass], [on Economical
configuration
mode(ECO)], [on High
efficiency(ECO+)],
[on battery], [battery low], [battery
fault],
[battery missing], [Fan fault],
[Summary Alarm]
Control
[enabled], [disabled]
commands
from serial
port
Output
[200V], [208V], [220V], [230V],
voltage
[240V], [autosensing]
Output
[50Hz], [60Hz], [autosensing]
frequency
Go to bypass
Battery test
Reset error state
Load segments
Sets parameters
Event list
[Type model] / [Part/Serial
number] / [UPS/firmware]
Default
English
disabled
enabled
01/01/2019
08:00
UPS ok
enabled
autosensing
autosensing