6.6 UPS startup and shutdown

Please make sure there is no load connected to the ups before the ups is
turned on and take on the load one by one after the UPS is turned on.
Take off all the connected loads before turning off the UPS.
6.6.1

Starting the UPS with utility

Verify that the total equipment ratings do not exceed the UPS capacity to
prevent an overload alarm.
Check all the connection is correct.
Power on the UPS, the fan begins to rotate. After that, the LCD will show
the default UPS status summary screen.
Pressing
button continuously for more than 1 second, the buzzer will
beep 300ms, UPS starts to turn on.
A few seconds later, the UPS turns into Line mode. If the utility power is
abnormal, the UPS will transfer to Battery mode without output
interruption of the UPS.
6.6.2

Starting the UPS on Battery

Before using this feature, the UPS must have been powered by utility
power with output enabled at least once.
After connecting the UPS with battery, you should wait 10s before
pressing
button for pre-charging the auxiliary power supply.
Battery start can be disabled. See "Start on battery" setting in user settings
refer to chapter on User Settings.