Technical Data - Siemens OpenAir GBB Series Technical Basics

Rotary actuators without spring return
Hide thumbs Also See for OpenAir GBB Series:
Table of Contents

Advertisement

AC 24 V supply
(SELV/PELV)
AC 230 V power supply
Functional data
Inputs
Positioning signal
for GBB/GIB13..1
Positioning signal
for GBB/GIB33..1
Positioning signal
for GBB16..1/GIB16..1..
Adjustable characteristic function
for GBB/GIB163.1,
GBB/GIB164.1
Outputs
Position indicator
for GBB/GIB16..1
Feedback potentiometer
for GBB/GIB135.1,
GBB/GIB335.1
Siemens
Smart Infrastructure
8

Technical data

Operating voltage
Frequency
Safety extra-low voltage (SELV) or
Protective extra-low voltage (PELV) as per
Requirements for external safety isolating transformer (100 % duty)
Supply line fuse
Power consumption GBB/GIB13..1: Running
GBB16.1/GIB16..1..: Running
GBB/GIB16..1: Holding
Operating voltage
Frequency
Supply line fuse
Power consumption: GBB/GIB33..1: Running
Nominal torque
Maximum torque (blocked)
Nominal rotary angle / max. rotary angle
Runtime for 90° rotary angle
Mechanical life
Operating voltage AC 24 V
Operating voltage AC 230 V (wires 4-6)
Input voltage (wires 8-2)
Current consumption
Input resistance
Max. permissible input voltage
Protected against faulty wiring
Neutral zone for nonadjustable characteristic function
for adjustable characteristic function
Hysteresis
for nonadjustable characteristic function
for adjustable characteristic function
Communication
Modbus RTU
Number of nodes
Address range
Transmission formats
Baudrates (kBaud)
Termination
Adjustable with 2 potentiometers:
Offset Uo
Span DU
Max. input voltage
Protected against faulty wiring
Output signal (wires 9-2)
Output voltage U
Max. output current
Protected against faulty wiring
Change of resistance (wires P1-P2)
Load
Max. sliding contact current
Rotary actuators without spring return GBB/GIB..1
Technical data
(wires 1-6)
(wires 1-7)
(wires 4-7)
AC 24 V ± 20 %
or AC 24 V class 2 (US)
50/60 Hz
HD 384
as per EN 61 558
max. 10 A
7 VA, 7 W
8 VA, 8 W
1.1 W
AC 230 V ± 10 %
50/60 Hz
max. 10 A
5 VA, 5 W
25 Nm GBB
35 Nm GIB
50 Nm GBB
75 Nm GIB
90 ° / 95° ± 2°
150 s (50 Hz) / 125 s (60 Hz)
5
10
cycles
clockwise
Counter-clockwise
clockwise
Counter-clockwise
DC 0...10 V
0.1 mA
> 100 kW
DC 35 V
max. AC 24 V
200 mV
2 % of DU
70 mV
0.7 % of DU
RS-485, not galvanically separated
Max. 32
1...247 / 255
Default: 255
1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2
Default: 1-8-E-1
Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 /
115.2
Default: Auto
120 Ω el. Switchable
Default: Off
DC 0...5 V
DC 2...30 V
DC 35 V
max. AC 24 V
DC 0...10 V
DC ± 1 mA
max. AC 24 V
0...1000 W
< 1 W
< 10 mA
CE1Z4626en