5 Commissioning

5.1 Programming pin and service LED

5.1.1 Addressing
5.1.2 Connection test
Siemens Industry, Inc.
Building Technologies
Prerequisites
Before commissioning a room operator unit, ensure that an application is
downloaded on to the connected room automation station, from where the
functions are downloaded to the room operator unit.
Automatically commissioning (1:1 connection)
In a 1:1 connection, which is only one room operator unit connecting to one room
automation station, the first time it is powered up using the KNX bus, the room
operator unit performs the commissioning procedure automatically.
When the commissioning is finished successfully, the room operator unit displays
the default operation page, which is defined in the application loaded in the room
automation station.
The devices come with a programming pin and a red service LED on the rear.
1. Briefly press the programming pin (<0.5 s).
a The device enters the programming mode; the service LED is continuously
on. The tool identifies the currently active device and assigns it.
2. After the device is commissioned, deactivate programming mode by shortly
pressing the programming pin (0.5 s). The service LED goes off.
NOTE: Programming mode returns to "disabled" each time the device restarts.
1. Press the programming pin (>5 s and <20 s) to test the KNX PL-Link
connection. After releasing the programming pin, testing of the KNX PL-Link
connection starts; the service LED flashes (1/4s on, 7/4s off).
After approximately 12 seconds, the test result is displayed:
Commissioning
Programming pin and service LED
A6V10958126_en--_a
5
15 | 29
2017-06-30