Electrical Installation - Dräger VarioGard Instructions For Use Manual

Gas warning system
Hide thumbs Also See for VarioGard:
Table of Contents

Advertisement

Installing the VarioGard system

Electrical installation

Electrical installation
– The VarioGard system wiring may only be routed and connected by an
electrician in accordance with the relevant regulations.
– Shielded cables are not required.
Only a limited number of system components such as transmitters can be
connected to a single central unit.
The various system components place different loads on the central unit.
The load is indicated in "busloads".
The individual system components (slaves) represent the following loads:
Slave
Transmitter with electrochemical Dräger
sensor
Relay module
Converter modulel
– for each 4 ... 20 mA loop connected which
is supplied by the VarioGard system bus
(i.e. maximum of 1 + 4 x 0.75 = 4 busloads)
The total of all the busloads must not exceed 16 without an additional power
supply. The maximum total cable lengths, depending on the total planned
busloads, are shown below:
Cross-section
JE-Y(St)Y 2 x 2 x 0,8 mm (0,5 mm
H05VV-R3 X 1,5 (NYM-O) 1.5 mm
Larger systems with cable lengths up to 1170 m or 24 busloads are also
possible, depending on the conditions prevailing in the individual systems.
Dräger Safety AG & Co. KGaA must be consulted with regard to the
technical details in such cases.
50
Busloads
1
2
1
0.75
2
4
2
)
900 m
810 m
540 m
2
1170 m 1170 m 1170 m 1170 m 1000 m 820 m
Number of busloads
6
8
10
400 m
320 m
270 m
12
14
16
230 m
200 m
700 m
610 m

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VarioGard and is the answer not in the manual?

Table of Contents