Installation

This section of the manual covers wiring and installa-
tion for the PMAC II panels.
2.1.

Location and Wiring

The following steps provide location and wiring in-
structions for the PMAC II panel. Figure 2-3 shows this
typical layout. Figure 2-5 shows the PMAC II internal wir-
ing connections.
Figure 2-1 - PMAC II Dimensions for the 16 and 20 Channel
Figure 2-2 - PMAC II Dimensions for the 28 Channel
1.
Mount the PMAC II panel in a central loca-
tion such as a motor or electrical room. The
panel should be where there is good air flow
(not in a closet). Keep a 6-12 inch clearance
on top and bottom for good air flow. The
room's ambient temperature should always
be below 100° F. Figure 2-1 and Figure 2-2
have the mounting dimensions.
4 • PMAC II I&O Manual
16.75"
Mounting
Holes
24.0"
Mounting
Holes
35.0"
WARNING: For proper cooling, the door
must be closed at times when unit is in opera-
tion.
2.
Provide 120 VAC (15 amp circuit) to the
PMAC II panel through a store circuit break-
er. See the layout design in Figure 2-3.
3.
Provide power to the case heaters from the
store circuit breaker panel through the
PMAC II panel terminal strip using #10-12
AWG wire, as shown in Figure 2-4.
Figure 2-3 - Typical Layout
Figure 2-4 - Typical Heater Wiring Layout
026-1501 Rev 6