Danfoss AK-SM 800 Operating Manual page 3

Hide thumbs Also See for AK-SM 800:

Advertisement

Operating Guide | AK-SM 800
© Danfoss | DCS (vt) | 2019.09
2. Rescan the system:
Having replaced the existing device with a new on the same address (084B4082 in this example),
Rescan the system.
Current Scan Status will now show the new detected device as 'Uncfg' .
Navigating to Configuration
to the newly added device to indicate that a wrong configuration file is in use for the newly added
device. Ensure the "Show only scanned Devices" is set to "Yes".
3. Setup the new device correctly:
Note: the correct EDF file for the new device MUST be installed!
Change the configuration file to the correct one and confirm that the 'Mismatch' message is gone.
Control
Refrigeration
Circuits, 'Mismatch' is shown next
AQ314725020974en-000101 | 3