SHP-30K-HV Series Installation manual Security Industrial Automate Telecom 30KW HVDC Power Supply High efficiency Intelligent...
Page 2
SHP-30K-HV series is a 30KW high efficiency AC/DC power supply. This series operates for the wide range three phase AC input n eutral is not needed, and offers the models with DC outputs (55V/115V/230V/380V) that mostly demanded by various industries. Can be working at ambient temperature up to 70 ℃...
Contents 1.Safety Guidelines 6.Communication Protocol PMBus Communication 2.Introduction Interface 2.1 Model Encoding CANBus Communication 2.2 Features Interface 2 3 Specification 6 3 . us Communication 2 4 Derating curve Interface 2 5 . Mechanical specification Value range and tolerance 3.Installation & Wiring 7.Protections and Trouble 3.1 Mounting Shooting...
1.Safety Guidelines 2.Introduction 2.1 Model Encoding Risk of electrical shock and energy hazard, all failure should be examined by a qualified technician. Please do not remove the case form the power supply by SHP - yourself. Please do not change any component on the unit or make any kind of Communication protocol option modification on it.
Features Specification △ ψ 3-wire / or Y 340~530VAC or 3 ψ 4-wire / Y 340~530VAC MODEL SHP-30K-55 SHP-30K-115 SHP-30K-230 SHP-30K-380 DC VOLTAGE (factory default) 55V 115V 230V 380V High efficiency up to 9 % CURRENT (factory default) 346A 261A 130.5A 2U high 19"-inch rack with forced air cooling RATED RANGE...
Installation Notes AC Power Connection A. Before any installation or maintenance work, please disconnect your ◎ / △ 3φ3-wire 340VAC~530VAC system from the utility. Ensure that it cannot be re-connected to the SHP-30K-HV utility inadvertently. B. Keep enough insulation distance between mounting screws and internal components of power supplies.
4.Panel and LED Indicator Pin Assignment of CN53 Panel Description -V(Signal) -V(Signal) AC input terminals: M6 screws are used; Recommended cable size: 3 - 10 AWG ; Recommended torque: 18kgf-cm. DC output terminals: M8 screws are used; Please refer to Section 3.3 for cable suggestion. Recommended torque: 80kgf-cm for the accessories come with the power supply.
4. Communication Address/ID Assignment Pin No. Function Description Each SHP 30K HV unit should have their unique and own device address to communicate over the Short: Termination resistors(120 ) For CANBus MODBus Ω 、 、 CANBus, PMBus or MODBus . SW51 and S 52 allow users to designate an address or ID for the...
5.Operation 5.3.2 PV (Output Voltage Programming) A.Set DIP switch 3 to ON position Inrush Current Limiting 1 2 3 Built-in AC inrush current limiting circuit. ● Since the inrush current limiting circuit mainly consists of a NTC ● thermistor and a relay, inrush current will be much higher than the B.Connect output of external DC source to PV+ and...
Iout 5.3.3 Communication Output voltage can be adjusted through communication interfaces: PMBus, CAN us or M us. Please refer to chapter 6 for detailed Non-Linear information. Non-Linear Output Current Adjustment Output current can be adjusted via PC and communication interface. ●...
Remote Control 5. . 5 2 SHP-30K-HV has the built-in active current sharing function and can be connected in parallel, up to 12 units or more, to provide higher output power as exhibited below : The power supply can be turned ON-OFF by using the "Remote ●...
Auxiliary Output 6.Communication Protocol uilt-in 12V/1. A auxiliary output ● There are two means to control the unit, analog signals and digital ● communication. Analog is the default setting for the unit, signals including PV, PC and SVR can be used immediately once receiving the unit.
Page 15
◎Definition of Table 6-1 Command BEh SYSTEM_CONFIG Command Command Transaction # of data Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Page Description Code Name Type Bytes High byte EEP_OFF EEP_CONFIG PAGE R/W Byte Page OPERATION R/W Byte Remote ON/OFF control Low byte OPERATION_INIT PM_CTRL...
Page 16
For example: Bit 2: P _OK : Primary PFC status 0=Primary PFC OFF or abnormal Vo_real (actual output voltage) = V x 2 , V is from READ_VOUT. 1=Primary PFC ON normally If VOUT_MODE = 0x17, meaning N is -9. READ_VOUT is 0x3000 →...
CANBus Communication Interface 3.Configure communication settings after power on. Enable Physical layer specification communication mode and set power ON when AC connected. ● This protocol follows CAN ISO-11898 with Baud rate of 250Kbps. Address(7 bit) Operation Command Code Data Data Frame ●...
Page 18
6.2.1 Message ID definition 6.2.2 Command list Message ID Description Command Command Transaction # of data Description Code Name Type Bytes 0x000C00XX SHP to Controller Message ID ON/OFF control 0x0000 OPERATION 0x000C01XX Controller to SHP Message ID ON: 01h/OFF: 00h 0x000C01FF Controller broadcasts to SHP Message ID(Writing only) Output voltage set...
Page 19
Bit 6 OP_OFF:DC status Command Command Transaction # of data Description 0=DC output turned on Code Name Type Bytes 1=DC output turned off Manufacture date 0x0086 MFR_DATE_B0B5 Manufacture serial number 0x0087 MFR_SERIAL_B0B5 Bit 7 HI_TEMP:Internal high temperature alarm Manufacture serial number 0=Internal temperature normal 0x0088 MFR_SERIAL_B6B11...
Page 20
Bit 4:7 IOUT Factor:The Factor of DC current ◎MFR_DATE_B0B5 ( 0x0086 ) is manufacture date (ASCII) 0x = Output current relevant commands not supported MFR_DATE_B0B5 is 180101, meaning 2018/01/01 0x4=0.001 Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 0x5=0.01 0x31...
Page 21
◎SYSTEM_CONFIG byte3: (0x00C2): Bit 0:3 IIN Factor:The Factor of AC input current Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 0x = AC input current relevant commands not supported High byte EEP_OFF EEP_CONFIG 0x4=0.001 Low byte OPERATION_INIT CAN_CTRL 0x5=0.01 Low byte: 0x6=0.1 Bit 0 CAN_CTRL:CANBus communication control status...
Page 22
.2. .2 Reading data or status 4.Set Output voltage to 56V The master reads operation setting from the unit with address "00". CAN ID Operation Command Code Data CAN ID DLC (data length) Command code 0x000C0100 0x04 0xE015 0x000C0101 0x0000 Command code: 0x 00 0 2 (VOUT_SET)
6 3 . us Communication Interface 6.3.3 Additional Address Definition Additional address is the slave ID of the device. Each SHP- 0K- The device supports M us RTU with the master-salve principle. unit should have their unique and own device address to Users are able to read and write parameters of the device through communicate over the bus.
Page 24
Table Register Command Function # of data Description address Name code Bytes Register Command Function # of data Description address Name code Bytes Manufacture model name 0x0086 MFR_MODEL_ 0x03 Remote ON/OFF control 0x0000 OPERATION 0x03、0x06 B0B5 ON: 0x0001 Manufacture model name 0x0089 MFR_MODEL_ 0x03...
Page 25
◎FAULT_STATUS (0x0040): ◎MFR_ID_B0B5 (0x0080 - 0x0082) is the first 6 codes of the Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 manufacturer's name (ASCII); MFR_ID_B6B11(0x0083 - 0x0085) is the High byte last 6 codes of the manufacturer's name (ASCII) Low byte EX: manufacturer's name is MEANWELL →...
Page 27
◎SYSTEM_STATUS byte1: (0x00C3): Bit 0:3 VIN Factor:The Factor of AC input voltage Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 0x0=AC input relevant commands not supported High byte 0x4=0.001 INITIA- Low byte EEPER DC_OK ADL_ON PFC OK M S / LSTATE 0x5=0.01 0x6=0.1...
Page 28
.3. .2 Read Input Register (FC=04) OPERATION_INIT:Pre-set value of power on operation command The request message specifies the starting register and quantity 0b00=Power OFF, pre-set 0x00(OFF) 0b01=Power ON, pre-set0x01(ON) (factory default) of registers to be read. For example: The master requests the 0b10=Pre-set is previous set value content of analog input register 0x0060 READ_VOUT...
Page 29
.Connect the DATA+/DATA- pins of the master to the corresponding 4.Set Output voltage to 56V. DATA+ (PIN15) and DATA- (PIN13)pins of the CN86 connector on the Data Address supply. It is recommended to establish a common ground for the Slave Address Function Code Data of the registe...
Value range and tolerance (2)Control parameters (1)Display parameters Model Display value range Tolerance Default PM: 00h OFF 01h ON Model Display value range Tolerance OPERATION CAN/MOD: 00h OFF 01h ON 31~2 6V ±0.55V READ_VIN 340~530V ±10V 115V -57 5~23V ±1.15V VOUT TRIM 230V -122~30V...
If you are unable to clarify the problem you are facing, please contact MEAN WELL or any of our distributors for repair service. to prevent damaging itself. The supply will restore automatically when AC voltage is back to a normal range.
※ MEAN WELL possesses the right to adjust the content of this manual. Please refer to the latest version of manual on our website. https://www.meanwell.com...