Temperature Input

The Series 3050 BTU flow monitor can accept inputs from either a pair of thermistors or RTDs . The inputs are labeled T1 and
T2 . Since the T1 sensor is used to convert the volumetric flow (Example: GPM) to the mass flow (Example: Lbs/Hr) used in the
BTU calculations, the sensor connected to T1 should be in the same supply or return line as the flow sensor .
The temperature inputs of the flow monitor are extremely versatile . In addition to the factory default two-wire 10k @ 77° F
Type II Thermistors and three-wire 100 Ω platinum RTDs, the unit can be programmed in the field for a wide variety of custom
RTDs and thermistors . See the
with any custom inputs .
June 2018
"Programming Flowcharts"
2 Wire
2 Wire
Th ermistor
Th ermistor
Located
in same
Supply
or
Return line
Flow Sensor
Figure 8: Wiring two-wire thermistors and RTDs
Di erent Color Wire
Same Colored 2 Wires
Di erent Wir e
3 Wire
3 Wire
RTD
RTD
T1
Located
in same
Supply
or
Return line
as
Flow Sensor
Figure 9: Wiring three-wire RTDs
DSY-UM-01668-EN-02
on
page 18 through page
1 TEMP 1 IN +
2 TEMP 1 IN -
3 TEMP 1 GND
4 SHIELD
Jumpers
5 TEMP 2 GND
6 TEMP 2 IN -
7 TEMP 2 IN +
1 TEMP 1 IN +
2 TEMP 1 IN -
3 TEMP 1 GND
4 SHIELD
5 TEMP 2 GND
6 TEMP 2 IN -
7 TEMP 2 IN +
25 . Contact the factory for assistance
Installation
Page 11